Control Panel Cooler
Details
This unit is used to reduce the internal temperature of control panels and control boxes. It removes heat from the cabinet and keeps electrical components within the allowed operating temperature range. Suni SAS series covers 300 W to 1200 W. It uses wall-mounted installation. It is used for small control boxes, control panels, and electrical cabinets.
Category
Cabinet Air Conditioner
Follow us & Contact us
Description
Heat Sources Inside a Control Panel

Heat inside a control panel does not come from one single component. Typical heat sources include:

  • PLC and I/O module
  • Power supply
  • Relay and contactor
  • Terminal block and wiring
  • Servo drive or stepper drive
  • Transformer
  • HMI or display

Total heat generation is the sum of all components. The panel surface area, ambient temperature, and sealing condition also affect internal temperature.

Panel Surface Temperature and Component Limit

Component life is affected by operating temperature. Before selecting a cooling method, confirm:

  • Maximum allowed ambient temperature of each component
  • Current measured panel internal temperature
  • Panel surface temperature
  • Ambient temperature around the panel
  • Panel sealing condition

If the measured internal temperature is close to the component limit, a cooling unit is required. If the internal temperature is only slightly above ambient, forced ventilation may be sufficient.

Air Conditioner or Fan Cooling

Condition

Recommended Method

Panel internal temperature slightly above ambient, clean air

Filter fan

Panel internal temperature 10°C–15°C above ambient

Fan with filter, larger air flow

Panel internal temperature 15°C or more above ambient

Compressor cooling unit

Dust, oil mist, or high humidity environment

Closed-loop compressor cooling unit

Panel sealing required

Closed-loop compressor cooling unit

For panels in dusty or oily environments, a closed-loop unit avoids dust entering the cabinet through ventilation openings.

 

Dust, Oil Mist, and Humidity

In dust, oil mist, or high humidity environments, the following points should be confirmed:

  • Protection level of the unit
  • Air inlet filter maintenance interval
  • Condensate drainage path
  • Panel sealing gasket condition
  • Corrosion resistance of the mounting bracket

If the environment has conductive dust or metal particles, confirm the panel sealing level before installation.

 

Condensate and Drainage

Condensate may form on the evaporator surface when panel internal temperature is low and ambient humidity is high. Confirm:

  • The drainage pipe is not blocked
  • The drainage outlet is away from electrical components
  • The drainage pipe has a downward slope
  • The drainage outlet is not in a location with water accumulation

If humidity is very high, discuss a condensate management solution at order confirmation.

 

Power Supply and Earthing

Power supply: 220V/1/50Hz.

Before connecting power, confirm:

  • Voltage and frequency match the nameplate
  • The power cable cross-section meets the unit current requirement
  • The earthing wire is connected
  • The power supply is stable and free of frequent voltage fluctuation

For panels powered by a common distribution unit, confirm the additional load does not exceed the distribution capacity.

 

Maintenance and Filter

Recommended maintenance:

Interval

Item

Monthly

Clean air inlet filter, check drainage pipe

Quarterly

Check unit running current, check sealing gasket

Every 6 months

Check temperature sensor, check fan blade

Every 12 months

Check refrigerant charge, check electrical connections

Keep spare parts: air filter, sealing gasket, drainage pipe, fan.

 

Common Fault Check

Symptom

Check

Panel internal temperature too high

Filter blockage, ambient temperature, panel heat generation

Water inside panel

Drainage pipe blocked, sealing gasket damaged

Unit does not start

Power supply, voltage, temperature controller setting

Noise increases

Fan blade, mounting screws, panel vibration

 

Specifications

Standard Configuration (SAS Series, Selected Models)

Parameter

Unit

SAS300

SAS450

SAS800

SAS1200

Cooling capacity

W

300

450

800

1200

Power supply

V/ph/Hz

220/1/50

220/1/50

220/1/50

220/1/50

Refrigerant

-

R22/R134A

Same

Same

Same

Protection level (internal/external)

IP

IP54/IP54

IP54/IP54

IP54/IP54

IP55/IP54

Noise

dB(A)

55

55

60

65

Dimensions (W×H×D)

mm

287×446×185

287×500×185

350×630×205

361×745×215

 

FAQ

Q: How do I know whether I need a compressor cooling unit or just a fan?

A: Measure the panel internal temperature and ambient temperature under normal working conditions. If the internal temperature is only slightly above ambient and the air is clean, a filter fan may be sufficient. If the internal temperature is 15°C or more above ambient, or if the environment has dust, oil mist, or high humidity, a compressor cooling unit is required.

Q: What causes water inside the control panel?

A: Water inside the panel usually comes from condensate that is not drained properly, or from a damaged sealing gasket. Check whether the drainage pipe is blocked or has an upward slope. Check whether the sealing gasket is deformed or aged. If humidity is very high, discuss a condensate management solution at order confirmation.

Hot Tags: control panel cooler, China control panel cooler manufacturers, suppliers, factory, control enclosure cooling air conditioner, frequency converter cabinet air conditioner, Industrial Electrical Cabinet Air Conditioner, industrial enclosure air conditioner, panel mounted air conditioner, power control cabinet air conditioner