Before selecting a model, confirm the following:
- Cabinet external dimensions (W×H×D)
- Cabinet wall thickness and material
- Total heat generation inside the cabinet
- Maximum ambient temperature around the cabinet
- Minimum ambient temperature around the cabinet
- Ambient humidity and dust condition
- Available space outside the cabinet
- Available space inside the cabinet
- Power supply voltage and frequency
- Whether drainage is possible
This list helps avoid selecting a model that cannot be installed or cannot reach the required temperature.
Check the internal layout before installation:
- Distance between the air outlet and nearby components
- Whether wiring or terminal blocks block the air path
- Whether the PLC or control module is in the direct air path
- Whether the cabinet has internal fans
- Whether the cabinet has a partition or inner door
If the cabinet has an inner door or partition, confirm the air outlet and return air inlet positions do not conflict with the inner door.
The unit can be mounted on different surfaces:
|
Mounting Surface |
Points to Confirm |
|
Side panel |
Panel strength, opening position, cable route |
|
Front door |
Door hinge direction, door opening angle, cable flexible section |
|
Top panel |
Rain protection, drainage route, maintenance access |
|
Rear panel |
Wall clearance, maintenance access |
For a cabinet door installation, the cable and drainage pipe need a flexible section to allow the door to open.
Before opening the cabinet, confirm:
- Panel thickness and material
- Whether the panel can support the unit weight
- Whether the opening position conflicts with internal components
- Whether the opening position conflicts with the door hinge or lock
- Whether a mounting frame or reinforcement plate is required
For thin panels or non-metal panels, a mounting frame or reinforcement plate may be required.
Confirm the route before installation:
- Power cable route from the distribution unit
- Cable length and protection conduit
- Drainage pipe route and downward slope
- Drainage outlet position
- Whether the drainage outlet is away from electrical components
If the cabinet is installed in a location without drainage, a condensate collection container may be required.
Confirm the sealing condition:
- Sealing gasket condition on the cabinet door
- Cable entry sealing
- Opening sealing after installation
- Air inlet filter condition
- Maintenance interval for filter cleaning
If the cabinet is in a dusty environment, confirm the sealing level before installation. If the cabinet has existing ventilation openings, confirm whether they need to be closed.
Reserve maintenance access around the unit:
- At least 500 mm in front of the unit for filter cleaning
- At least 300 mm on the air outlet side
- Space for opening the electrical cover
- Space for drainage pipe inspection
If the cabinet is installed in a narrow space, confirm the maintenance access before installation.
After installation, record the following:
- Cabinet internal temperature at the air return inlet
- Cabinet internal temperature at the air outlet
- Ambient temperature
- Unit running current
- Cabinet door sealing condition
- Drainage pipe condition
If the cabinet internal temperature cannot reach the set point, check heat generation, air path, sealing, and ambient temperature.
Standard Configuration (SAS Series, Selected Models)
|
Parameter |
Unit |
SAS300 |
SAS500 |
SAS800 |
SAS1200 |
|
Cooling capacity |
W |
300 |
500 |
800 |
1200 |
|
Cabinet internal temperature range |
°C |
+25 to +38 |
+25 to +38 |
+25 to +38 |
+25 to +38 |
|
Cabinet external temperature range |
°C |
-5 to +55 |
-5 to +55 |
-5 to +55 |
-5 to +55 |
|
Power supply |
V/ph/Hz |
220/1/50 |
220/1/50 |
220/1/50 |
220/1/50 |
|
Refrigerant |
- |
R22/R134A |
Same |
Same |
Same |
|
Protection level (internal/external) |
IP |
IP54/IP54 |
IP54/IP54 |
IP54/IP54 |
IP55/IP54 |
|
Noise |
dB(A) |
55 |
55 |
60 |
65 |
Q: Can the unit be installed on the cabinet door?
A: Yes, but confirm the door hinge direction, door opening angle, and cable route. The power cable and drainage pipe need a flexible section so the door can open without pulling the cable or pipe. Confirm the door panel strength can support the unit weight.
Q: What should be checked if the cabinet internal temperature cannot reach the set point?
A: Check the following: actual total heat generation, air outlet and return air inlet blockage, cabinet sealing condition, ambient temperature around the cabinet, and air inlet filter condition. If the actual heat generation is higher than the design value, select a larger model.
Hot Tags: small enclosure air conditioner, China small enclosure air conditioner manufacturers, suppliers, factory, Air Conditioning Fresh Air Unit, cabinet air conditioner evaporator fan, control enclosure air conditioner, electrical control box air conditioner, frequency converter cabinet air conditioner, high temperature cabinet air conditioner