Portable Chilled Water System

Send Inquiry
Portable Chilled Water System
Details
This unit is a compact cooling system that combines refrigeration, water storage, and circulation. It supplies chilled water to equipment that needs a stable inlet water temperature. Suni SCA air-cooled series can be configured for this purpose. Cooling capacity covers 2.7 kW to 30 kW. It is used in equipment debugging, temporary production lines, and workshops where a fixed cooling water system is not yet available. The system can be connected to the equipment water inlet and outlet, and put into operation after power connection.
Category
Industrial Chiller
Follow us & Contact us
Description
Temperature Stability Under Variable Heat Load

When equipment heat load changes during operation, the chilled water temperature may fluctuate. The system uses a water tank to buffer temperature changes. A larger water tank reduces temperature fluctuation but increases cooling time and occupies more space.

Selection needs to consider:

  • Equipment heat load
  • Allowed chilled water temperature fluctuation
  • Initial water temperature
  • Target water temperature
  • Cooling time

If heat load fluctuates greatly, a larger water tank or a model with higher cooling capacity can be selected. Provide the heat load curve and allowed temperature range for technical calculation.

Water Circuit Connection

The system has a chilled water outlet and return water inlet. Connect them to the equipment water circuit. Before operation, check:

  • Water circuit is filled
  • No air in the piping
  • No leakage at connections
  • Water flow direction is correct
  • Return water temperature is within the allowed range

If the equipment has an existing water circuit, confirm the connection size and flow demand. SCA series connection size is DN15 to DN40. If the existing piping size does not match, a reducer solution can be discussed at order confirmation.

Operation and Protection

The system includes high/low pressure, overload, anti-freeze, time delay, over-temperature, and water flow protection. These protections act when water flow stops, ambient temperature is too low, or voltage fluctuates.

Before starting the system, confirm:

  • Power supply matches the nameplate
  • Water circuit is filled and air is removed
  • Ambient temperature is above the anti-freeze set point
  • Ventilation around the unit is sufficient

If the water flow protection acts, check the water pump, water circuit valve, and piping blockage before restarting.

 

Specifications

Standard Configuration (SCA Air-Cooled Series, Selected Models)

Parameter

Unit

SCA-01

SCA-03

SCA-06

SCA-10

Cooling capacity

kW

2.7

8.5

18

30

Power supply

V/ph/Hz

220/1/50

380/3/50

380/3/50

380/3/50

Input power

kW

1.34

3.19

6.13

10.54

Water pump power

kW

0.37

0.55

0.55

1.1

Water tank volume

L

20

50

80

200

Connection size

DN

15

25

25

40

Air flow

m³/h

1500

4000

7500

12000

Refrigerant

-

R22/R134a/R404

Same

Same

Same

Noise

dB(A)

58

60

62

65

Unit weight

kg

75

150

200

260

Dimensions (L×W)

mm

600×520

1000×550

1250×650

1650×790

Complete parameters for SCA-02, SCA-04, SCA-05, and SCA-08 are available on other product pages or upon inquiry.

 

Maintenance and Troubleshooting

Symptom

Check

Water flow protection acts

Water pump, valve, piping blockage

Cooling capacity drops

Condenser fin dust, ambient temperature, refrigerant charge

Temperature fluctuation too large

Water tank volume, heat load change, water flow

Noise increases

Fan blade, water pump, loose panel

Daily maintenance:

  • Clean condenser fins
  • Check water circuit for leakage
  • Check pump running current
  • Confirm power supply voltage is stable

 

FAQ

Q: What should be confirmed before connecting the unit to equipment?

A: Confirm equipment water inlet and outlet size, chilled water flow demand, allowed inlet water temperature, and return water temperature range. Also confirm the site power supply and available space around the unit. If the equipment has a plate heat exchanger or small channel, confirm the water quality and filter requirements.

Q: What causes large chilled water temperature fluctuation during operation?

A: Common causes include: water tank volume too small for the heat load, equipment heat load changes faster than the system response, insufficient chilled water flow, or air in the water circuit. Check the water circuit first, then confirm whether the selected model matches the actual heat load curve.

Hot Tags: portable chilled water system, China portable chilled water system manufacturers, suppliers, factory, Industrial Air Cooled Water Chiller, industrial brine cooling system, Industrial Oil Chiller, industrial temperature control system, industrial water cooled chiller, Machine Tool Chillers